As soon as people learned that we were replacing theCR1000 dataloggerwith theCR1000X datalogger, they asked us these questions: “Can I load a program I wrote for my CR1000 into a CR1000X?” and “Will the CR1000X fit in the same space as my CR1000?”
Easy answer—yes, mostly. Let me explain. The upgrade improvements in the CR1000X are not simply cosmetic. The CR1000X is a completely new product from the ground up. However, because the programming and functions are very similar between the CR1000X and CR1000, the replacement is fairly straightforward.
In the following sections, I’ll highlight the similarities and differences of the two data loggers that you should know about.
Physically, replacing a CR1000 with a CR1000X is simple. The size of the CR1000X is the same as the CR1000.
Here is where things get different. Removable terminal strips on the CR1000X wiring panel provide a quick and effective way to quickly swap data loggers without removing sensor wires or the entire wiring panel. The complete wiring panel and data logger are still separate components. Like the CR1000, the CR1000X is in a sealed, protective enclosure, shielded from direct electrical damage through the terminal and port connectors. The wiring panel becomes the first line of protection for the data logger. This increases the probability that the data is saved if catastrophic damage should occur. And in most cases, the repairs are limited to the wiring panel.
CR1000 Wiring Panel
CR1000X Wiring Panel with Terminal Strip Removed
The CR1000X wiring panel is not generally intended to be interchanged with another CR1000X wiring panel.
Because the CR1000X can measure analog current directly (0 to 20 mA or 4 to 20 mA), the wiring panel is not designed to be interchangeable.
If the wiring panel of the CR1000X becomes damaged and a new wiring panel is required, the CR1000X wiring panel must be calibrated with the CR1000X measurement module to maintain current-measurement accuracy.
The CR1000 wiring panel can be interchanged with another CR1000 wiring panel.
For the CR1000, any wiring panel can be used with any CR1000 datalogger.
The CR1000X and CR1000 wiring panels cannot be interchanged.
Although there are significant additions to the CR1000X program instructions that are not available in the CR1000, in most cases you can load your program written for the CR1000 into a CR1000X with minor instruction changes. The most notable of these changes is in the analog measurement instructions. I will use the Differential Measurement,VoltDiff(), to illustrate.
Parameter | CR1000 | CR1000X | ||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
VoltDiff(Dest,1,mV5000,1,True ,0,_60,1.0,0) | VoltDiff(Dest,1,mV5000,1,True ,0,60,1.0,0) | |||||||||||||||||||||||||||||||||||||||||||||||
Dest | The Dest parameter is a variable in which to store the results of the measurement. | Same as the CR1000. | ||||||||||||||||||||||||||||||||||||||||||||||
Reps | The Reps parameter is the number of times the measurement should be made. Measurements are made on consecutive channels. If the Reps parameter is greater than 1, the Dest parameter must be a variable array. | Same as the CR1000. | ||||||||||||||||||||||||||||||||||||||||||||||
Range | The Range parameter is the expected voltage range of the input from the sensor. The following range options are available:
|
The Range parameter is the expected voltage range of the input from the sensor. The following range options are available:
|
||||||||||||||||||||||||||||||||||||||||||||||
DiffChan | The DiffChan parameter is the number of the differential channel on which to make the first measurement. If the Reps parameter is greater than 1, the additional measurements will be made on sequential channels. | Same as the CR1000. | ||||||||||||||||||||||||||||||||||||||||||||||
RevDiff | A constant is entered for the RevDiff parameter to determine whether the inputs are reversed and a second measurement made. This function removes any voltage offset errors due to the data logger measurement circuitry, including operational input voltage errors.
|
Same as the CR1000. | ||||||||||||||||||||||||||||||||||||||||||||||
SettlingTime | The SettlingTime parameter is the amount of time to delay after setting up a measurement and before making the measurement. | Same as the CR1000. | ||||||||||||||||||||||||||||||||||||||||||||||
Integ (for CR1000) fN1 (for CR1000X) |
The Integ parameter is the amount of time, in microseconds, to integrate a signal for the channel being measured. Three options are available:
|
The fN1(first notch frequency) parameter determines the lowest frequency that will be eliminated or notched out by the sinc filter. Any value between 5 Hz and 93.75 kHz can be entered, but common options for filtering noise are the following:
|
||||||||||||||||||||||||||||||||||||||||||||||
Mult, Offset | Both the Mult and Offset parameters are a constant, variable, array, or expression by which to scale the results of the measurement. With a multiplier (mult) of 1 and an offset of 0, the output is in millivolts. | Same as the CR1000. |
推荐给你:For programming assistance, watch the"CRBasic | Help System" video.
There are two quick ways I use to convert a CR1000 program to a CR1000X program.
Replacing your current CR1000 dataloggers with our new CR1000X dataloggers should be a fairly straightforward process, and I hope the information in this article is helpful to you.If you have any questions I didn’t address, please post them below.
Comments
Ekpyro|09/23/2018 at 03:52 PM
With the CR1000, one could use 'Com2' as the communication port for the 'SerialOut' instruction, and this would transmit on pin C3. This appears to have changed with the CR1000X. How can one convert this line for CR1000X?:
`SerialOut(Com2, ...`
Robin D|09/24/2018 at 12:22 PM
谢谢你的关心,Ekpyro。一定要指定数控3 for the port. Using this will work just like it did for the CR1000.
kirving|09/25/2018 at 02:00 PM
In getting my first CR1000X program to compile, after using CR1000 for some time, I see there are a few differences, including 'Com1' changing to 'ComC1' as mentioned above. Another difference seems to be that control port references, e.g. in the portSet() instruction, use 'C3' vs '3' for the CR1000. I don't see any mention of this in the pdf manual. Is a resource describing programming details available for the CR1000X?
Big Fish|09/26/2018 at 08:47 AM
You are correct, other than what is mentioned in the blog, there is not a resourece available that describes the programming in detail.
Ron Muzzi|04/10/2019 at 08:54 AM
ThePulseCountinstruction was also changed and is not backward compatible. Specifically, thePConfigoption uses different values than the CR1000. It would be helpful if you would provide a document that simply lists all the instructions that have changed, especially those that are not backward compatible. It wouldn't even need details about the change, as we can figure that out from the CRBasic Editor help system. Thanks!
Big Fish|04/10/2019 at 11:02 AM
Great suggestion. I will make sure we post the list.