One Helpful Method to Diagnose a Modbus Communication Problem

byPaul Smart| Updated: 03/08/2017 | Comments: 4

Search the Blog


Subscribe to the Blog

Set up your preferences for receiving email notifications when new blog articles are posted that match your areas of interest.


区域/应用程序

Product Category

Activity

Corporate / News

Enter your email address:



Suggest an Article

Is there a topic you would like to learn more about? Let us know. Please be as specific as possible.

Leave this field empty

Modbus

Have you ever set up a Campbell Scientific data logger as a Modbus server and discovered that your data was not arriving at your SCADA system as you expected? You may have quickly realized two things: troubleshooting the communication problem is not an easy task, and there are many different approaches you can take. In this article, I’ll quickly share with you one method that I have found to be both helpful and a time-saver.

Campbell Scientific data loggers provide measurement data to SCADA (supervisory control and data acquisition) systems throughout the world. This is often accomplished by configuring the data logger as a Modbus TCP/IP server, which we discussed in the“How to Access Live Measurement Data Using Modbus” blog article.

Normally, the process of setting up the communication between your data logger and SCADA system is smooth, but there are occasions when technicians in the field discover that the data is not arriving at the SCADA system as expected. At times like this, you may wonder: Where is the problem with the communication? Is the problem at the SCADA system (Modbus client), the data logger (Modbus server), or somewhere in-between?

Inour last Modbus blog article, we used an example with a data logger that was set up to make analog measurements and provide the data to the SCADA system through the Modbus TCP/IP protocol.

Modbus communication with analog measurement and datalogger to a SCADA system

我们将使用同样的例子。SCADA system is set up to poll your data logger every second for the contents of its Modbus registers. Your data logger, in turn, makes analog measurements and then stores them in its Modbus Holding and Input registers every second.

But what if your SCADA system does not successfully receive data from your data logger? What can you do now? You can use Campbell Scientific’sDevice Configuration Utility (DevConfig)to monitor the incoming traffic to your data logger. This helps determine if the polls from your SCADA system are arriving at your data logger, and if your data logger is responding.

Follow these steps to use DevConfig to see the Modbus polls:

  1. Open the Device Configuration Utility, and connect to your data logger.
  2. Select theTerminaltab on the far right.

    Terminal tab selected in DevConfig

    Click the DevConfig screen for a larger image.

  3. 按下Enterkey on your keyboard until you see a prompt on your screen.
  4. TypeW, and press theEnterkey.

    DevConfig screen

    Click the DevConfig screen for a larger image.

  5. To selectTCP/IP, type13and press theEnterkey.
  6. On your screen, you will be askedASCII (Y)?TypeN, and press theEnterkey.
  7. If your data logger is not receiving any Modbus polls, your screen will likely look something like this:

    DevConfig with ASCII question

    Click the DevConfig screen for a larger image.

Note that there is no Modbus traffic being detected over TCP/IP. The only message on the screen is “hit ESC to exit, any other key to renew timeout.” This scenario could indicate one or more of the following conditions:

  • The SCADA system is not polling the data logger.
  • The SCADA system is polling a different IP address.
  • The data logger has been assigned an incorrect IP address.
  • A cable is not plugged in.
  • Modbus traffic is being blocked by the network.

Your data logger may be set up and programmed completely fine, but if it is not receiving the polls from the SCADA client, the data will not arrive where it is expected. At this point, focus your troubleshooting efforts on the SCADA network, client configuration, etc. (areas outside of the data logger).

Special Note:In instances like this, you may see traffic over TCP/IP that is not Modbus traffic, such as PakBus traffic from a LoggerNet Server if there is a LoggerNet-to-data-logger connection on the network.

After you’ve addressed your network or SCADA system problems, a successful trace looks like this:

A successful trace in DevConfig

Click the DevConfig screen for a larger image.

The easiest way to recognize the Modbus TCP traffic and distinguish it from other protocols is that the transmission from the client always starts with an identifier in the first two bytes. In our example, the first poll that was recognized in the trace started with00 16. The data logger, in turn, responded with this same unique identifier (00 16). The next time the client polled, it used an identifier of00 17, and the data logger responded with00 17.

Special Note:有一个Modbus TCP流量之间的区别nd Modbus RTU traffic. The easiest way to recognize Modbus RTU traffic is to look for a transmission from the client that starts with the Modbus server address and function code. The server response will also start with its address and function code.

If you can see Modbus polls coming from the client (T), but no responses from the data logger (R), it is time to check the configuration and programming of the data logger. You may have an error in your setup such as:

  • The data logger is not programmed as a Modbus server.
  • The data logger has been given a Modbus server ID that does not match what the client is polling.

At this point, you’ll need to dig into your data logger setup for further troubleshooting.

Conclusion

Using DevConfig to watch the TCP/IP traffic on your data logger is a great way you can quickly check to see if things are working as expected. This method often saves a lot of time because you can more quickly identify the communication problem.

If you have any questions about this troubleshooting method, please post them below.


Share This Article



About the Author

保罗聪明Paul Smart is the Vice President of Sales and Marketing at Campbell Scientific, Inc. His first experience with Campbell equipment came soon after graduating from college while working on a series of plant-growing experiments conducted on the International Space Station. Paul enjoys leveraging unique Campbell Scientific technology to solve challenging measurement problems. He has a bachelor’s degree in Electrical Engineering and an MBA. Paul also enjoys the outdoors, fly fishing, and spending time with his family.

View all articles by this author.


Comments

smile|04/05/2017 at 01:16 PM

Dear Paul, basically I do not understand, the reasons because with a commercial RS232 868Mhz radio-modem on port COM4 of a CR1000 OS31, the connection does not work with MODBUS protocol.
The strange situation is:
1) on the RS232 port with the commercial radio-modem all works fine (modbus and pakbus)
2) on the COM4 port with the commercial radio-modem pakbus works fine
3) on RS232 port and COM4 with your RF416 radio (trasparent mode) all works fine (modbus and pakbus).
Before spending time with sniffer on serial port and investigate with oscilloscope, these situations can suggest to you some idea?
Unfortunately for local issues (distance, vegetation and other) can not use the your radio RF416.
During the tests (in our office) that I have mentioned above, nothing changes, only:
- the program instruction “MODBUSSLAVE” and “SERIALOPEN” between the RS232 Vs COM4
- DB9 cable for RSR232 Vs cable with individual pins (TX, RX and GND) for the COM4
These are the lines that use in program.
SerialOpen(COM4,9600,0,5000,1000)
ModbusSlave (Com4,9600,1,modln(),modbus_port,0)

I can say that, when it does not work (commercial radio-COM4-MODBUS), the data arrives at the remote radio, in fact I can see the green LED RX that lights up, but the CR1000 does not respond and the red LED TX remains off.

I tried to increase the delay, even up to 5 seconds,
“SerialOpen(COMRS232,9600,0,5000000,1000)”
“ModbusSlave (ComRS232,9600,1,modln(),modbus_port,0)”
but I see that the CR1000 always immediate answer, of course, the working situation 1 (Commercial radio, RS232 MODBUS).

I hope that this series of tests can give you some suggestions, of course I am available in case of questions.

Thanks in advance

Regards

Smile

smile|04/05/2017 at 01:21 PM

Sorry Paul, this was a premise that I forgot to put in my previous post.

Dear Paul, perhaps you are the person that can help me a real headache. I've already opened a discussion on this subject in the forum and I also wrote to Franco Casule UK. Let's see who is able to help me before :-), unfortunately I have some urgency. What I'm writing is a synthesis of the two messages that I already wrote in the forum and Franco.

smile|04/05/2017 at 01:24 PM

Of course, I am available for other information useful for diagnosis

Paul Smart|04/10/2017 at 10:36 AM

Sorry for the delay in responding. It looks like JDavis has answered your question in the forum already concerning the potential issue with timing delays coming from the radio. Good luck going forward and thanks for reading.

Pleaselog in or registerto comment.